ICPDAS M-7017Z

Levertijd:
2~7 dagen
SKU
M-7017Z

10/20-channel Analog Input Module with High Voltage Protection

 
● 3000 VDC Isolated analog input.
● 24-bits sigma-delta ADC to provide excellent accuracy.
● Software calibration
● Dual Watchdog

 

The MICPDAS Analog Input Module M-7017Z is a data acquisition and control module that support Modbus RTU and DCON protocols. With the Modbus RTU protocol, it can easily communicate with most popular SCADA/HMI software and PLC. It has the same form factor as the I-7000 series.

 

ICPDAS Analog Input Module M-7017Z has software configurable channels-- from 10 differential channels into 20 single ended channels. Both voltage and current are accepted: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA , 0 ~ 20 mA, and 4 ~ 20 mA. No external resistor needed for measuring the current, all you have to do is to open the shell first and finish the setting by jumper.

Measuring the current is as simple as you think! The M-7017Z also passes 240 Vrms overvoltage protection for differential inputs and 150Vrms overvoltage protection for singleended inputs, 3000 VDC intra-module isolation, ±4 kV contact ESD protection, ±4 kV EFT protection for power, and ±1 kV EFT protection for RS-485. The sampling rate of M-7017Z is changeable. There are fast mode and normal mode for your consideration. Fast Mode is 60 Hz with 12-bit resolution. Normal Mode is 10 Hz with 16-bit Resolution.

Meer informatie
Art.nr.
M-7017Z
Fabrikant
ICPDAS
Analog Input
Input Channels 10 differential or 20 single-ended (Note1), software selectable
Input Type
±500 mV, ±1 V, ±5 V, ±10 V
±20 mA ,0 ~ 20 mA, 4 ~ 20 mA (jumper selectable)
Resolution 16-bit (Normal Mode) / 12-bit (Fast Mode)
Sampling Rate 10 samples/sec (Normal Mode) / 60 samples/sec (Fast Mode) total
Accuracy ±0.1% (Normal Mode) / ±0.5% (Fast Mode) or better
Bandwidth 15.7 Hz (Normal Mode) / 78.7 Hz (Fast Mode)
Zero Drift ±20 uV/°C
Span Drift ±25 ppm/°C
Input Impedance* Voltage: 2 MΩ (Differential), 1 MΩ (Single-ended) /Current: 125 Ω
Common Mode Rejection 86 dB min.
Normal Mode Rejection 100 dB
Overvoltage Protection Differential: 240 Vrms, Single-ended: 150 Vrms
ESD Protection 4 kV Contact for each terminal, and 8 kV Air for random point
EFT Protection 4 kV to Power, and 1 kV to RS-485
Individual Channel Configuration Yes
Intra-module Isolation, Field to Logic 3000 VDC
* Differential mode can be used for voltage input and current input.
Single-Ended mode can be used for voltage input only.
Interface
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
LED Indicators
LED Power/Communication
Protocol
Support Modbus and DCON Protocol Yes
Power
Input +10 ~ +30 VDC
Power Consumption 2.0 W
Omgeving
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -40 °C ~ +85 °C
Humidity 5 ~ 95%, non-condensing
Mijn vraag gaat over: ICPDAS M-7017Z
U bent wellicht ook geïnteresseerd in de volgende producten:
To Top