CAN2000D Series
- ICPDAS CAN-2026C - CANopen Slave Module with 6-channel AI, 2-channel AO, 1-channel DO and 2-channel DI.
6-ch Analog Input, 2-ch Analog Output, 2-ch Digital Input and 1-ch Digital Output CANopen Slave Module
● I/O Channels: 6AI, 2AO, 2DI and 1DO
● Analog Input Type: +/-150mV, +/-500 mV, +/-1V, +/-5 V, +/-10 V +/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Current measurement with external 125Ω resistor required )
● Analog Output Type: +0 V ~ +5 V, +/-5 V, +0 V ~ +10 V, +/-10 V
● Analog Input sample rate: 60 Samples/Sec. (Total)
● Digital Input Type: Sink
● Digital Output Type: Sink
● Analog Input Resolution: 16-bit
● Analog Input Accuracy: +/-0.1% FSR
● Analog Output Resolution: 12-bit
● Analog Output Accuracy: +/-0.1% FSR
● ESD Protection: +/- 4kV, Contact for each terminal
● Intra-module Isolation: Field to logic 3000 VDC
- ICPDAS EIP-2060
Isolated 6-ch DI and 6-ch Relay Output EtherNet/IP I/O module
● Transfer protocol: EtherNet/IP
● Powerful 32-bit MCU handles efficient network traffic
● 10/100 Base-TX Ethernet, RJ-45 x 2 (Auto-negotiating, auto MDI/MDIX, LED Indicators)
● Support ARP,TCP, UDP, ICMP, DHCP, BOOTP and TFTP protocols
● Easy firmware update via Ethernet
● Removable terminal block connector
● RoHS compliant with Halogen-free
● LED display to indicate the I/O status - ICPDAS CAN-2015C
CANopen Slave Module of 8-channel RTD Inputs
● Default EDS file
● Passed the validation of CiA CANopen Conformance
● Test tool
● ESD Protection 4 KV Contact for each channel
● Support Power Supply +10 ~ +30 VDC
● Support CiA-301 v4.02, CiA-401 v2.1
● Support Dynamic PDO - ICPDAS CAN-2018D
DeviceNet Slave Module of 8-channel thermocouple input
● DeviceNet general I/O slave devices
● Comply with DeviceNet specification Volume I,
● Release 2.0 & Volume II, Release 2.0, Errata 5
● Group 2 Only Server (non UCMM-capable)
● Support Predefined Master/Slave Connection Set
● Connection supported:
● 1 connection for Explicit Messaging
● 1 connection for Polled I/O
● 1 connection for Bit-Strobe I/O connection
● Support DeviceNet heartbeat and shutdown messages
● Provide EDS file for DeviceNet master interface - ICPDAS CAN-2017C
8-channel 14-bit analog input module
● NMT Slave
● NMT Error Control support Guarding and Heartbeat
● Provide default EDS file
● Passed the validation of CiA CANopen Conformance
● Test tool
● Sampling mode support normal and fast mode
● ESD Protection 4 KV Contact for each channel
● Support Power Supply +10 ~ +30 VDC
● Support CiA DS-301 v4.02, DSP-401 v2.1
● Support Dynamic PDO - ICPDAS CANopen module of 4-channel 14-bit analog output module - CAN-2024C
CANopen module of 4-channel 14-bit analog output module
● NMT Slave
● Read-Back Accuracy ±1% of FSR
● Provide default EDS file
● ESD Protection 4 kV Contact for each channel
● Support Power Supply +10 VDC ~ +30 VDC
● Support CiA DS-301 v4.02, DSP-401 v2.1
● Support PDO Mapping - ICPDAS CAN-2054D
8-channel isolated sink/source digital input and 8-channel isolated open-collector digital output module
● DeviceNet general I/O slave devices
● Comply with DeviceNet specification Volume I, Release 2.0 & Volume II, Release 2.0, Errata 5
● Group 2 Only Server (non UCMM-capable)
● Support Predefined Master/Slave Connection Set
● Connection supported (1 connection for Explicit Messaging, 1 connection for Polled I/O, 1 connection for Bit-Strobe I/O connection)
● Support DeviceNet heartbeat and shutdown messages
● Provide EDS file for DeviceNet master interface - ICPDAS CAN-2057D
DeviceNet Module of 16-channel Isolated Open Collector Digital Output
● DeviceNet general I/O slave devices
● Group 2 Only Server (non UCMM-capable)
● Support Predefined Master/Slave Connection Set
● Connection supported (1 connection for Explicit Messaging, 1 connection for Polled I/O, 1 connection for Bit-Strobe I/O connection)
● Support DeviceNet heartbeat and shutdown messages
● Provide EDS file for DeviceNet master interface
● Support Application: Drive Relay, Resistance Load
● ESD Protection 4 kV Contact for each channel - ICPDAS CAN-2053D
DeviceNet Module of 16-channel Isolated Sink/Source Digital Input
● DeviceNet general I/O slave devices
● Group 2 Only Server (non UCMM-capable)
● Support Predefined Master/Slave Connection Set
● Connection supported (1 connection for Explicit Messaging, 1 connection for Polled I/O, 1 connection for Bit-Strobe I/O connection)
● Provide EDS file for DeviceNet master interface
● Support Application: PNP, NPN, TTL, and Relay Contact
● ESD Protection 4 kV Contact for each channel - ICPDAS CAN-2088D
CAN bus Remote I/O module with CANopen Protocol of 8-Channel PWM and 8-Channel High Speed Counter
● Hardware-controlled PWM output
● PWM output frequency: 0.2 Hz ~ 500 kHz with 0.1%~99.9% duty cycle
● PWM Output Modes: software trigger / hardware trigger
● Trigger each PWM output individually or all PWM outputs synchronously
● Support Burst output mode and Continue output mode
● Provide 32-bit 500 kHz high-speed counter for each DI channel
● Pass the validation of DeviceNet conformance test
● Provide EDS file for DeviceNet master interface