ICPDAS MDR-60-48

Levertijd:
2~7 dagen
SKU
MDR-60-48

48 V/1.25 A, 60 W Single Output Industrial DIN-Rail Power Supply

● Universal AC input/Full range
● Protections: Short circuit / Overload / Overvoltage
● Cooling by free air convection
● Can be installed on DIN-Rail TS-35/7.5 or 15
● NEC class 2 / LPS compliant (48V only)
● LED indicator for power on
● DC OK relay contact
● No load power consumption <0.75 W
● 100% full load burn-in test

Notes:

 

1. All parameters NOT specially mentioned are measured at 230 VAC input, rated load and 25 of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 uf & 47 uf parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.

Meer informatie
Art.nr.
MDR-60-48
Fabrikant
ICPDAS
Input
Voltage Range
85 ~ 264 VAC
120 ~ 370 VDC
Frequency Range 47 ~ 63 Hz
Efficiency (Typical) 87%
AC Current (Typical)
1.8 A/115 VAC
1 A/230 VAC
Inrush Current (Typical)
Cold Start 30 A/115 VAC
60 A/230 VAC
Leakage Current <1 mA / 240 VAC
Output
DC Voltage 48 V
Rated Current 1.25 A
Current Range 0 ~ 1.25 A
Rated Power 60 W
Ripple & Noise (max.) 200 mVp-p
Voltage ADJ range 48 ~ 56 V
Voltage Tolerance ±1.0%
Line Regulation ±1.0%
Load Regulation ±1.0%
Setup, Rise Time
500 ms, 30 ms/230 VAC
500 ms, 30 ms/115 VAC at full load
Protection
Overload
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Overvoltage
57.6 ~ 64.8 V
Protection type : Shut down o/p voltage, re-power on to recover
Function
DC OK Signal Relay contact rating (max.): 30 V/1 A resistive
Safety & EMC
Safety Standards UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only)
Withstand Voltage
I/P-O/P 3 KVAC 
I/P-FG 1.5 KVAC
O/P-FG 0.5KVAC
Isolation Resistance
I/P-O/P >100 MΩ / 500 VDC 25 °C 70% RH
I/P-FG
O/P-FG
EMI Conduction & Radiation Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B
Harmonic Current Compliance to EN61000-3-2,-3
EMS Immunity Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
DC OK Relay Contact
Contact Close When the output voltage reaches the adjusted output voltage.
Contact Open When the output voltage drop below 90% output voltage.
Contact Ratings (max.) 30V/1A resistive load
Algemeen
MTBF
299.2K hrs min.
MIL-HDBK-217F (25 °C)
Omgeving
Operating Temperature -20 °C ~ +70 °C (Refer to output load derating curve)
Operating Humidity 20 ~ 90% RH non-condensing
Storage Temperature -40 °C ~ +85 °C
Storage Humidity 10 ~ 95% RH
Temperature Coefficient ±0.03%/°C (0 °C ~ 50 °C)
Vibration
Component : each along X, Y, Z axes
Mounting : Compliance to IEC60068-2-6 10 ~ 500Hz, 2G 10min./1cycle, period for 60min.
Mechanical
Dimensions (w x h x d) 40 x 90 x 100mm