ICPDAS DR-120-24

Levertijd:
2~7 dagen
SKU
DR-120-24-CR

120 W Single Output Industrial DIN-Rail Power Supply

● Universal AC input/Full range
● Protections: Short circuit / Overload / Overvoltage
● Cooling by free air convection
● Can be installed on DIN rail TS-35/7.5 or 15
● UL 508(industrial control equipment) approved
● LED indicator for power on
● Fixed switching frequency at 55 KHz
● 100% full load burn-in test

Notes:

 

1. All parameters NOT specially mentioned are measured at 230 VAC input, rated load and 25 of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

 

 

Output Derating  Static Characteristics (24V)
https://fieldworks.magento-ontwikkeling.nl/media/imageproducts/icpdas/DR-120-48_01.jpg https://fieldworks.magento-ontwikkeling.nl/media/imageproducts/icpdas/DR-120-48_02.jpg
Meer informatie
Art.nr.
DR-120-24-CR
Fabrikant
ICPDAS
Input
Voltage Range
88 ~ 132 VAC/176 ~ 264 VAC by switch
248 ~ 370 VDC
Frequency Range 47 ~ 63Hz
Efficiency (Typical) 85%
AC Current (Typical)
2.6 A/115 VAC
1.6 A/230 VAC
Inrush Current (Typical)
Cold Start 20 A/115 VAC
40 A/230 VAC
Leakage Current <3.5 mA / 240 VAC
Output
DC Voltage 24 V
Rated Current 5 A
Current Range 0 ~ 2.5 A
Rated Power 120 W
Ripple & Noise (max.) 100mVp-p
Voltage ADJ. Range 24 ~ 28 V
Voltage Tolerance ±1.0%
Line Regulation ±0.5%
Load Regulation ±1.0%
Setup, Rise Time
500 ms, 70 ms/230 VAC
500 ms, 70 ms/115 VAC at full load
Hold Up Time (Typical)
36 ms/230 VAC
32 ms/115 VAC at full load
Protection
Overload
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Overvoltage
29 ~ 33 V
Protection type : Shut down o/p voltage, re-power on to recover
Safety & EMC
Safety Standards UL508, UL60950-1, TUV EN60950-1 Approved
Withstand Voltage
I/P-O/P 3KVAC
I/P-FG 1.5KVAC
O/P-FG 0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500 VDC
EMI Conduction & Radiation Compliance to EN55011,EN55022 (CISPR22) Class B
Harmonic Current Compliance to EN61000-3-2,-3
EMS Immunity Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
DC OK Relay Contact
Contact Close When the output voltage reaches the adjusted output voltage
Contact Open When the output voltage drop below 90% output voltage
Contact Ratings (max.) 30V/1A resistive load
Algemeen
MTBF
136.8Khrs min.
MIL-HDBK-217F (25°C)
Omgeving
Working Temperature -10 °C ~ +60 °C (Refer to output load derating curve)
Working Humidity 20 ~ 90% RH non-condensing
Storage Temperature, Humidity -20 °C ~ +85 °C, 10 ~ 95% RH
Temperature Coefficient ±0.03%/°C (0 °C ~ +50 °C)
Vibration 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Mechanical
Dimensions (w x h x d) 65.5 x 125.2 x 100mm