ICPDAS I-8024W
4-channel 14-bit Analog Output Module (Gray Cover)
With different communication interface, the I/O modules can be classified to high communication speed (Parallel bus) 8K series modules and low communication speed (serial interface) 87K series modules.
| There are two types of I/O modules, Parallel and Serial. The parallel modules (I-8 Series) are high-speed modules and support MCU (Main Control Unit) only. | |
| Item | I-87K Series |
| Communication Interface | Parallel Bus |
| Protocol | - |
| Communication Speed | Fast |
| DI with Latched Function | - |
| DI with Counter Input | - |
| Power On Value | - |
| Safe Value | - |
| Programmable Slew-rate for AO Module | - |
High Profile VS Low Profile
With different form factor, I/O modules can be classified to high profile and low profile. Basically, high profile and low profile modules that with same item number also have same I/O channel number.
For example: I-8054 and I-8054W both has 8 DI and 8 DO.
Except I/O channel number, other specifications could be different. You have to double check whether the specifications suit your application.
For example: For I-8054W, its DI logic high level is +10 ~ +50V. But for I-8054, it is +3.5 ~ +30V

| Output Channels | 4 | ||
| Output Type | ±10 V, 0 ~ +20 mA | ||
| Resolution | 14-bit | ||
| Accuracy | ±0.1% of FSR for voltage output ; ±0.2% of FSR for current output | ||
| Readback Accuracy | ±1% of FSR | ||
| Zero Drift |
|
||
| Span Drift | ±20 ppm/°C | ||
| Programmable Output Slope | 0.125 ~ 2048 mA/second | ||
| Voltage Output Capability | 10 V@20 mA | ||
| Max. Current Load Resistance | External +24 V: 1050 Ω | ||
| Power-Up and SafeValue | Yes | ||
| 4KV ESD Protection | Yes, Contact for each terminal | ||
| Intra-module Isolation, Field to Logic | 3000 VDC |
| 1 LED | Power |
| Power Consumption | 0.4 A@5 VDC = 2 W, ±5% |
| Dimensions (w x l x h) | 30 x 102 x 115 mm |
| Operating Temperature | -25 °C ~ +75 °C |
| Storage Temperature | -30 °C ~ +75 °C |
| Humidity | 5 ~ 95%, Non-condensing |