Wij gebruiken cookies om uw ervaring beter te maken. Om te voldoen aan de cookie wetgeving, vragen we uw toestemming om de cookies te plaatsen. Meer informatie.
ICPDAS CAN-8424
DeviceNet Embedded Device with 4 I/O Expansions
● DeviceNet Version: DeviceNet Specification Volume I & II, Release 2.0
● Number of Nodes: 64 max.
● Baud Rate: 125K, 250K, 500K bps
● Support Message Groups: Predefined Master/Slave Connection set (Group 2 only Server)
● I/O Operating Modes: Poll, Bit-Strobe, Change of State / Cyclic
● Device Heartbeat & Shutdown Message
● Produce EDS file Dynamically
● No. of Fragment I/O: 128 Bytes max. (Input / Output)
● MAC ID Setting by Rotary Switch
● Baud Rate Setting by Rotary Switch
DeviceNet is one kind of the network protocols based on the CAN bus and mainly used for embedded network for machine control, such as textile machinery, printing machines, injection molding machinery, or packaging machines, etc. DeviceNet is a low level network that provides connections between simple industrial devices (sensors, actuators) and higher level devices (controllers). It allows direct peer to peer data exchange between nodes in an organized and, if necessary, deterministic manner. DeviceNet defines a connection-based scheme to facilitate all application communications. A DeviceNet connection provides a communication path between multiple endpoints. The endpoints of a connection are applications that need to share data.
The ICPDAS 8000 Series I/O Unit CAN-8424 main unit based on the modular design offers many good features to the users and provides more flexibility in data acquisition and control system.
In addition, ICP DAS also presents a CAN-8424 Utility tool to allow users to configure and create the EDS file for the specific IO modules plugged in.
Therefore, users can easily apply the ICPDAS 8000 Series I/O Unit CAN-8424 embedded controller in DeviceNet network.
APPLICATIONS:
● Automotive
● Food & Beverage
● Packaging
● High-speed Assembly
● Pulp & Paper
● Semiconductor Fabrication
● Control System
UTILITY:
ICPDAS 8000 Series I/O Unit CAN-8424 main unit can be plugged in the DCON(/I-8K/I-87K) IO modules to create a customized DeviceNet slave device and application. Before applying the CAN-8424 in DeviceNet applications, users must understand the relationship between these DeviceNet applications and assembly objects within ICPDAS 8000 Series I/O Unit CAN-8424 DeviceNet slave. In order to allow user to easy apply the device on the network, ICP DAS also provides the CAN-8423 Utility tool to configure the IO connection path, assembly and application objects information and create the EDS file of the device.
DESIGN FLOWCHART:
The following simple steps show how to use CAN-8x24 in the DeviceNet protocol.
CPU | 80186, 80MHz or compatible |
SRAM/Flash/EEPROM | 512KB / 512KB / 16KB |
NVRAM | 31 bytes (battery backup, data valid for up to 10 years) |
RTC (Real Time Clock) | Yes |
Watchdog | CPU build-in |
Expansion Slot | 4 slots |
Controller | NXP SJA1000T with 16MHz clock | ||
Transceiver | NXP 82C250 | ||
Channel Number | 1 | ||
Connector | 5-pin screwed terminal block (CAN_L, CAN_SHLD, CAN_H, N/A for others) | ||
Baud Rate | 125k, 250k, 500k | ||
Transmission Distance | Depend on Baud Rate (for example, max. 500m at 125kbps) | ||
Isolation | 3000V DC for DC-to-DC, 2500Vrms for photo-couple | ||
Terminator Resistor | Jumper for 120Ω terminator resistor | ||
Specification | ISO-11898-2, CAN 2.0A and CAN 2.0B | ||
Protocol |
|
COM 1 | RS-232 (For configuration) |
COM 1 Connector | 9-pin male D-Sub (DTE: RxD, TxD, RTS, CTS, DTR, DSR, RI, GND) |
Round LED | PWR LED, NET LED, MOD LED |
Power Supply | Unregulated +10 ~ +30 VDC |
Protection | Power reverse polarity protection, Overvoltage Brownout protection |
Power Consumption | 2.5W |
Installation | DIN-Rail Mounting |
Dimensions (w x l x h) | 188 x 132 x 91mm |
Operating Temperature | -25 °C ~ 75 °C |
Storage Temperature | -40 °C ~ 80 °C |
Humidity | 5 ~ 95% RH, non-condensing |