Signal Conditioning Module DI-8B33

Levertijd:
3~4 weken
SKU
DI-8B33

DI-8B33 Isolated True RMS Input Module (100 mV ~ 300 V RMS Input Range)

● Interfaces RMS Voltage (100 mV to 300 V)
● Designed For Standard Operation With Frequencies of 45 Hz ~ 1 kHz (Extended Range to 20 kHz)
● Compatible With Standard Current and Potential Transformers
● ±0.25% Factory Calibrated Accuracy (Accuracy Class 0.2)
● 1500 Vrms Continuous Transformer Based Isolation
● Input Overload Protected to 480 V Max (Peak AC and DC) or 10A RMS Continuous
● ANSI/IEEE C37.90.1-1989 Transient Protection

DI-8B modules are an optimal solution for monitoring real-world process signals and providing high level signals to a data acquisition system. Each DI-8B33 module isolates, filters and amplifies a True RMS input signal and provides an analog voltage output. Signal filtering is accomplished with a three-pole filter optimized for time and frequency response which provides 70dB of normal-mode-rejection at 60Hz. One pole of this filter is on the field side of the isolation barrier for anti-aliasing, and the other two are on the system side. A special input circuit on the DI-8B33 module provides protection against accidental connection of power-line voltages up to 30VAC. Isolation is provided by optical coupling to suppress transmission of common mode spikes or surges. The module is powered from +5VDC, ±5%. The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.